Fan coil heating restored via BMS weather-compensation reset - The Pinnacle, Reading
Reading RG1 · The Pinnacle, 20 Tudor Road, Reading, RG1 1NH
Completed October 2026
Diagnostic: Insufficient daytime heating reported from the fan coil units at the managed residential/office block.
Remedial works: Inspected the Belimo valve actuator, reviewed the Trend BMS heating controls, pump status and temperature trends, and adjusted the weather-compensation settings. Heating flow temperature increased from 50.4 C to 56.5 C and monitored room temperature rose from 18.5 C to 20.9 C. Status: heating improved during attendance; a Trend BMS engineer is recommended to investigate the daytime setpoint reduction and Pump 1 fault.